ZGS11-ZF-630~2000/0-0.69 Wind Power Generate Combined Transformer
Summary:
Product Category:
Tel:
ZGS11-ZF-630~2000/0-0.69 Wind Power Generate Combined Transformer
Details
Model & Symbol Meaning

●Low Voltage Rated Voltage (kV)
●High Voltage Rated Voltage (kV)
●Transformer Rated Capacity (kVA)
●Terminal Type Wind Generator
●Performance Level Code
●Combined Share Cabinet Type Three Phase
Executive Standards
●JB/T10217-2013
●GB1094.1-2013
●GB3804.1-2017
●GB7251.1-20 13
Overview
ZGS-ZF-D/O series combined transformer satisfy power supply requires, based on 10kV combined transformer, customized design for nation grid with international technology. Company designed transformer load switch, high voltage fusion tube install inside transformer. Use transformer isolation liquid as whole product isolation dielectric and heat dissipation dielectric.
Product suit for 50Hz, 35/0.69 and 10/0.69kV wind generation system. Transformer rated capacity is 630~ 2000kVA, only for wind power generator.
Operation Condition
●Altitude: s3000m
●Environment temperature range
●Temperature: Maximum monthly mean temperature +30°C, Minimum monthly mean temperature +20°C
●Relative humidity: the daily average is not more than 95%, and the monthly average is not more than 90%
●Shockproof level: horizontal acceleration 0.4m/s2
●Installation environment: the surrounding air is not subject to corrosion, flammable gas and other obvious pollution, the installation site without violent vibration
Primary Technical Parameter
Wind Generator Combined Transformer Technical Parameters
|
Rated Capacity (kva) |
Voltage Combination |
Connection Group Mark |
No-loadLoss(kw) |
Load Loss(kw) |
Short Circuit Impedance |
No-load Current |
Body Weight{NA) |
Oil Weight(kVA) |
Total Weight(kVA) |
Outline Dimension L×W×H(mm) |
||
|
High Yoltage |
Tapping Range |
Low Voltage |
||||||||||
|
630 |
10.5 10 6.3 |
±2×2.5 |
0.69 |
Dyn11 |
810 |
6200 |
4.5 |
0.9 |
1230 |
790 |
3320 |
2050×930×1900 |
|
800 |
980 |
7500 |
0.8 |
1390 |
830 |
3580 |
2050×1170×1900 |
|||||
|
1000 |
1150 |
10300 |
0.7 |
1750 |
870 |
3800 |
2050×1250×1900 |
|||||
|
1250 |
1360 |
12000 |
0.6 |
1980 |
1020 |
3950 |
2050×250×1900 |
|||||
|
1600 |
1640 |
14500 |
0.6 |
2335 |
1190 |
4615 |
2050×1250×1900 |
|||||
|
2000 |
1980 |
19500 |
5.5 |
0.6 |
3850 |
1200 |
6290 |
2050×2600×100 |
||||
Date from table is for reference, final dimension based on drawing
Wind Generator Combined Transformer Technical Parameters
|
Rated Capacity (kva) |
Voltage Combination |
Connection Group Mark |
No-loadLoss(kw) |
Load Loss(kw) |
Short Circui Impedance |
No-Load Current |
Body Weight[kVA] |
Oil Weight(kVA) |
Total Weight(kVA) |
Outline Dimension L×W×H(mm) |
||
|
High Yoltage |
Tapping Range |
Low Voltage |
||||||||||
|
630 |
35 36.75 38.5 |
±2×2.5 |
0.69 |
Dyn11 |
820 |
7820 |
6.5 |
0.9 |
1640 |
1220 |
3760 |
1270×1695×2200 |
|
800 |
980 |
9350 |
0.8 |
1875 |
1370 |
4210 |
2390×1890×2200 |
|||||
|
1000 |
1160 |
11480 |
0.7 |
2370 |
1505 |
5020 |
2480×1950×2200 |
|||||
|
1250 |
1380 |
13860 |
0.6 |
1645 |
1650 |
5610 |
2540×2180×2200 |
|||||
|
1600 |
1660 |
16580 |
0.6 |
3270 |
1760 |
6525 |
2740×2300×2200 |
|||||
|
2000 |
2850 |
19500 |
0.6 |
4500 |
1200 |
7500 |
2800×2300×2200 |
|||||
Date from table is for reference, final dimension based on drawing
Keyword: