SC(B) Series Epoxy Resin Pouring Dry Type Transformer
Summary:
Product Category:
Tel:
SC(B) Series Epoxy Resin Pouring Dry Type Transformer
Details
Executive Standards
●IEC 60076-11:2004
●GB 1094.11-2007
●GB/T10228-2015
Operation Condition
●The highest temperature: + 40 °C
●The highest average daily temperature + 30°C
●The highest annual average temperature: + 20 °C
●The lowest temperature:-5 °C (applicable to indoor transformer)
●The lowest temperature -30 °C (applicable to outdoor type transformer)
●Altitude: ≤1000m
●Humidity: the relative humidity of the surrounding air should be less than 93%. Water droplets should not appear on the surface of the coil
●Our company can provide users with special conditions of use of the products.
Overview
Dry type transformer is a transformer whose core and winding are not immersed in insulating liquid. Electrical dry type transformer design according to IEC international standards and the existing national standards, its manufacturing technology always keep synchronized advancement of the international level, the main production 35 kv and dry type transformer products below include epoxy resin casting dry-type transformer, impregnation class H insulation dry type transformer and dry type amorphous alloy transformer. It has performance of no leakage of oil and gas, safety, environmental protection, low noise.
Range Of Application
The products are mainly applicable to commercial buildings, high-rise buildings, airports, industrial and mining enterprises, power plants, oil platforms, subways and tunnels and other important places with special fire protection requirements.The product can also be combined with switchgear to form a box-type substation.
Coil
●F class isolation high voltage coil: coil adopt with half hard enameled wire, hardness could choice between 120~210Mpa. Isolated material mix with silicon powder and epoxy resin, it has excellent heat wave resistance ability, resist burning, no position gas, great heat dispersion, coil temperature rise speed low. Specially fit for resin high voltage coil.
●H class isolated high voltage coil: adopt with OMEX paper wrap flat copper wire and continue winding draft, strong machine strength, excellent on heat dispersion, process by VPIvacuum pressure equipment, and with special formula go through many times dip and bake solidify.
●Low voltage coil: coil mainly made by foil, and on the winding machine go through inner argon protection weld, high accuracy, reliable weld and no need for external weld. Solution from imbalance ampere-turn, improve heat dispersion and increase resist short circuit ability.
Subassemblies
●Protective Case
Protective case have normal steel, stainless steel and aluminum alloy for choice. And it has type for indoor or outdoor. For example IP20 protective case, can prevent size over 12mm solid material entry, suit for indoor installation. IP23 case not only can do that and also can prevent 60 degree angle water flow inside, suitable for outdoor.
●Temperature Control Device
Transformer temperature control device adopt PIC nonlinearity resistance and PT100 linear resistance dual sensor method, LED temperature display, saving highest temperature, automatically send alarm switch off signal, automatic or manual turn on/off fan, according to requirements different control device can be provide.
●Air cooling system
Transformers generally use natural air cooling (AN), can continuously output rated capacity. Air cooling system can be configured according to user requirements. The fan is automatically controlled by the thermometer to ensure that the transformer is qualified for temperature rise when the rated load is exceeded.
Quality assurance system
Reliable quality is the fundamental guarantee for our products to win customers. Our company has passed the international IS09001 quality management standard certification. Our company has established a customer-centered quality management chain, which ensures strict control of all links from order acceptance to product delivery, installation and operation, and earnestly provides after-sales service. From raw materials into the factory, production and processing are equipped with full-time personnel for inspection. Each production process implements the system of self-inspection, mutual inspection and special inspection. After the final assembly of the product, the factory test shall be carried out strictly according to the product standard. Advanced inspection technology and equipment, ensure to provide customers with quality and reliable products.
SC(B)10-30KVA~2500KVA Unexcited Voltage Regulation Distribution Dry Type Transformer
|
Model |
Rated Capacity (kva) |
VoltageCombination&TappingRange |
Connection Group Mark |
No-load Loss(kw) |
Load Loss(KW) On DifferentIsolated System Temperature |
No-Load Current |
Short Circuit Resistance |
||||
|
High Voltage |
High Voltage Tapping Range |
Low Voltage |
130℃(B)(100℃) |
155℃(F)(120℃) |
180℃(H)(145℃) |
||||||
|
SC10-30 |
30 |
6 6.3 6.610 10.5 11 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
0.190 |
0.670 |
0.710 |
0.760 |
2.0 |
4.0 |
|
SC10-50 |
50 |
0.270 |
0.940 |
1.00 |
1.07 |
2.0 |
|||||
|
SC10-80 |
80 |
0.370 |
1.29 |
1.38 |
1.48 |
1.5 |
|||||
|
SC10-100 |
100 |
0.400 |
1.48 |
1.57 |
1.69 |
1.5 |
|||||
|
SC10-125 |
125 |
0.470 |
1.74 |
1.85 |
1.98 |
1.3 |
|||||
|
SC10-160 |
160 |
0.540 |
2.00 |
2.13 |
2.28 |
1.3 |
|||||
|
SCB10-200 |
200 |
0.620 |
2.37 |
2.53 |
2.71 |
1.1 |
|||||
|
SCB10-250 |
250 |
0.720 |
2.59 |
2.76 |
2.96 |
1.1 |
|||||
|
SCB10-315 |
315 |
0.880 |
3.27 |
3.47 |
3.73 |
1.0 |
|||||
|
SCB10-400 |
400 |
0.980 |
3.75 |
3.99 |
4.28 |
1.0 |
|||||
|
SCB10-500 |
500 |
1.16 |
4.59 |
4.88 |
5.23 |
1.0 |
|||||
|
SCB10-630 |
630 |
1.30 |
5.61 |
5.96 |
6.40 |
0.85 |
6.0 |
||||
|
SCB10-800 |
800 |
1.52 |
6.55 |
6.96 |
7.46 |
0.85 |
|||||
|
SCB10-1000 |
1000 |
1.77 |
7.65 |
8.13 |
8.76 |
0.85 |
|||||
|
SCB10-1250 |
1250 |
2.09 |
9.10 |
9.69 |
10.3 |
0.85 |
|||||
|
SCB10-1600 |
1600 |
2.45 |
11.0 |
11.7 |
12.5 |
0.85 |
|||||
|
SCB10-2000 |
2000 |
3.05 |
13.6 |
14.4 |
15.5 |
0.70 |
|||||
|
SCB10-2500 |
2500 |
3.60 |
16.1 |
17.1 |
18.4 |
0.70 |
|||||
|
Model |
Rated Capacity (kva) |
Weight(kg) |
OutlineDimension(mm) |
Gauge(mm) |
|
|
Body size LxWxH |
Enclosure size LxWxH |
||||
|
SC10-30 |
30 |
220 |
630×530×700 |
|
350×350 |
|
SC10-50 |
50 |
370 |
720×550×705 |
|
350×350 |
|
SC10-80 |
80 |
440 |
695×610×890 |
|
400×400 |
|
SC10-100 |
100 |
530 |
850×500×720 |
|
500×400 |
|
SC10-125 |
125 |
565 |
1010×900×1125 |
|
550×820 |
|
SC10-160 |
160 |
705 |
1010×900×1140 |
|
550×820 |
|
SCB10-200 |
200 |
960 |
1020×730×1050 |
1500×1250×1650 |
550×660 |
|
SCB10-250 |
250 |
1130 |
1050×730×1075 |
1500×1250×1650 |
550×660 |
|
SCB10-315 |
315 |
1245 |
1100×730×1140 |
1550×1250×1650 |
660×660 |
|
SCB10-400 |
400 |
1280 |
1140×730×1130 |
1550×1250×1650 |
660×660 |
|
SCB10-500 |
500 |
1560 |
1210×890×1195 |
1600×1250×1650 |
660×820 |
|
SCB10-630 |
630 |
1710 |
1300×890×1190 |
1700×1250×1650 |
660×820 |
|
SCB10-800 |
800 |
2035 |
1380×890×1320 |
1800×1300×1700 |
660×820 |
|
SCB10-1000 |
1000 |
2480 |
1450×890×1350 |
1900×1400×1800 |
820×820 |
|
SCB10-1250 |
1250 |
2730 |
1500×890×1410 |
1900×1400×1800 |
820×820 |
|
SCB10-1600 |
1600 |
3525 |
1640×1020×1475 |
2000×1500×2000 |
820×950 |
|
SCB10-2000 |
2000 |
3945 |
1750×1020×1580 |
2100×1600×2000 |
820×950 |
|
SCB10-2500 |
2500 |
4860 |
1910×1120×1960 |
2300×1600×2200 |
1070×1070 |
Note: The above data is for reference only. Our company reserves the right to change the data. Our company provides non-standard products according to user requirements.
|
Model |
Rated Capacity (kva) |
Voltage Combination&Tapping Range |
Connection GroupMark |
No-load Loss(kw) |
Load Loss(KW) On DifferentIsolated System Temperature |
No-Load Current |
Short Circuit Besistance |
||||
|
High Voltage |
High Voltage Tapping Range |
Low Voltage |
130℃(B)(100℃) |
155℃(F)(120℃) |
180℃(H)(145℃) |
||||||
|
SC11-30 |
30 |
6 6.3 6.610 10.5 11 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
0.170 |
0.670 |
0.710 |
0.760 |
2.0 |
4.0 |
|
SC11-50 |
50 |
0.240 |
0.940 |
1.00 |
1.07 |
2.0 |
|||||
|
SC11-80 |
80 |
0.330 |
1.29 |
1.38 |
1.48 |
1.5 |
|||||
|
SC11-100 |
100 |
0.360 |
1.48 |
1.57 |
1.69 |
1.5 |
|||||
|
SC11-125 |
125 |
0.420 |
1.74 |
1.85 |
1.98 |
1.3 |
|||||
|
SC11-160 |
160 |
0.480 |
2.00 |
2.13 |
2.28 |
1.3 |
|||||
|
SCB11-200 |
200 |
0.550 |
2.37 |
2.53 |
2.71 |
1.1 |
|||||
|
SCB11-250 |
250 |
0.640 |
2.59 |
2.76 |
2.96 |
1.1 |
|||||
|
SCB11-315 |
315 |
0.790 |
3.27 |
3.47 |
3.73 |
1.0 |
|||||
|
SCB11-400 |
400 |
0.880 |
3.75 |
3.99 |
4.28 |
1.0 |
|||||
|
SCB11-500 |
500 |
1.04 |
4.59 |
4.88 |
5.23 |
1.0 |
|||||
|
SCB11-630 |
630 |
1.17 |
5.61 |
5.96 |
6.40 |
0.85 |
6.0 |
||||
|
SCB11-800 |
800 |
1.36 |
6.55 |
6.96 |
7.46 |
0.85 |
|||||
|
SCB11-1000 |
1000 |
1.59 |
7.65 |
8.13 |
8.76 |
0.85 |
|||||
|
SCB11-1250 |
1250 |
1.88 |
9.10 |
9.69 |
10.3 |
0.85 |
|||||
|
SCB11-1600 |
1600 |
2.20 |
11.0 |
11.7 |
12.5 |
0.85 |
|||||
|
SCB11-2000 |
2000 |
2.74 |
13.6 |
14.4 |
15.5 |
0.70 |
|||||
|
SCB11-2500 |
2500 |
3.24 |
16.1 |
17.1 |
18.4 |
0.70 |
|||||
|
Model |
Rated Capacity (kva) |
Weight(kg) |
Outline Dimension(mm) |
Gauge(mm) |
|
|
Body size LxWxH |
Enclosure size LxWxH |
||||
|
SC11-30 |
30 |
220 |
630×530×700 |
|
350×350 |
|
SC11-50 |
50 |
370 |
720×550×705 |
|
350×350 |
|
SC11-80 |
80 |
440 |
695×610×890 |
|
400×400 |
|
SC11-100 |
100 |
530 |
850×500×720 |
|
500×400 |
|
SC11-125 |
125 |
565 |
1010×900×1125 |
|
550×820 |
|
SC11-160 |
160 |
705 |
1010×900×1140 |
|
550×820 |
|
SCB11-200 |
200 |
960 |
1020×730×1050 |
1500×1250×1650 |
550×660 |
|
SCB11-250 |
250 |
1130 |
1050×730×1075 |
1500×1250×1650 |
550×660 |
|
SCB11-315 |
315 |
1245 |
1100×730×1140 |
1550×1250×1650 |
660×660 |
|
SCB11-400 |
400 |
1280 |
1140×730×1130 |
1550×1250×1650 |
660×660 |
|
SCB11-500 |
500 |
1560 |
1210×890×1195 |
1600×1250×1650 |
660×820 |
|
SCB11-630 |
630 |
1710 |
1300×890×1190 |
1700×1250×1650 |
660×820 |
|
SCB11-800 |
800 |
2035 |
1380×890×1320 |
1800×1300×1700 |
660×820 |
|
SCB11-1000 |
1000 |
2480 |
1450×890×1350 |
1900×1400×1800 |
820×820 |
|
SCB11-1250 |
1250 |
2730 |
1500×890×1410 |
1900×1400×1800 |
820×820 |
|
SCB11-1600 |
1600 |
3525 |
1640×1020×1475 |
2000×1500×2000 |
820×950 |
|
SCB11-2000 |
2000 |
3945 |
1750×1020×1580 |
2100×1600×2000 |
820×950 |
|
SCB11-2500 |
2500 |
4860 |
1910×1120×1960 |
2300×1600×2200 |
1070×1070 |
Note: The above data is for reference only. Our company reserves the right to change the data. Our company provides non-standard products according to user requirements.
|
Model |
Rated Capacity (kva) |
VoltageCombination&TappingRange |
Connection Group Mark |
No-load Loss(kw) |
Load Loss(KW) On DifferentIsolated System Temperature |
No-Load Current |
Short Circuit Besistance |
||||
|
HighVoltage |
High Voltage Tapping Range |
Low Voltage |
130℃(B)(100℃) |
155℃(F)(120℃) |
180℃(H)(145℃) |
||||||
|
SC13-30 |
30 |
6 6.3 6.610 10.5 11 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
0.135 |
0.605 |
0.640 |
0.685 |
2.0 |
4.0 |
|
SC13-50 |
50 |
0.195 |
0.845 |
0.900 |
0.965 |
2.0 |
|||||
|
SC13-80 |
80 |
0.265 |
1.160 |
1.240 |
1.330 |
1.5 |
|||||
|
SC13-100 |
100 |
0.290 |
1.330 |
1.415 |
1.520 |
1.5 |
|||||
|
SC13-125 |
125 |
0.340 |
1.565 |
1.665 |
1.780 |
1.3 |
|||||
|
SC13-160 |
160 |
0.385 |
1.800 |
1.915 |
2.050 |
1.3 |
|||||
|
SCB13-200 |
200 |
0.445 |
2.135 |
2.275 |
2.440 |
1.1 |
|||||
|
SCB13-250 |
250 |
0.515 |
2.330 |
2.485 |
2.665 |
1.1 |
|||||
|
SCB13-315 |
315 |
0.635 |
2.945 |
3.125 |
3.355 |
1.0 |
|||||
|
SCB13-400 |
400 |
0.705 |
3.375 |
3.591 |
3.850 |
1.0 |
|||||
|
SCB13-500 |
500 |
0.835 |
4.130 |
4.390 |
4.705 |
1.0 |
|||||
|
SCB13-630 |
630 |
0.965 |
4.975 |
5.290 |
5.660 |
0.85 |
6.0 |
||||
|
SCB13-800 |
800 |
1.095 |
5.895 |
6.265 |
6.715 |
0.85 |
|||||
|
SCB13-1000 |
1000 |
1.275 |
6.885 |
7.315 |
7.885 |
0.85 |
|||||
|
SCB13-1250 |
1250 |
1.505 |
8.190 |
8.720 |
9.335 |
0.85 |
|||||
|
SCB13-1600 |
1600 |
1.765 |
9.945 |
10.555 |
11.320 |
0.85 |
|||||
|
SCB13-2000 |
2000 |
2.195 |
12.240 |
13.005 |
14.005 |
0.70 |
|||||
|
SCB13-2500 |
2500 |
2.595 |
14.535 |
15.455 |
16.605 |
0.70 |
|||||
|
Model |
Rated Capacity (kva) |
Weight(kg) |
OutlineDimension(mm) |
Gauge(mm) |
|
|
Body size LxWxH |
Enclosure size LxWxH |
||||
|
SC13-30 |
30 |
220 |
630×530×700 |
|
350×350 |
|
SC13-50 |
50 |
370 |
720×550×705 |
|
350×350 |
|
SC13-80 |
80 |
440 |
695×610×890 |
|
400×400 |
|
SC13-100 |
100 |
530 |
850×500×720 |
|
500×400 |
|
SC13-125 |
125 |
565 |
1010×900×1125 |
|
550×820 |
|
SC13-160 |
160 |
705 |
1010×900×1140 |
|
550×820 |
|
SCB13-200 |
200 |
960 |
1020×730×1050 |
1500×1250×1650 |
550×660 |
|
SCB13-250 |
250 |
1130 |
1050×730×1075 |
1500×1250×1650 |
550×660 |
|
SCB13-315 |
315 |
1245 |
1100×730×1140 |
1550×1250×1650 |
660×660 |
|
SCB13-400 |
400 |
1280 |
1140×730×1130 |
1550×1250×1650 |
660×660 |
|
SCB13-500 |
500 |
1560 |
1210×890×1195 |
1600×1250×1650 |
660×820 |
|
SCB13-630 |
630 |
1710 |
1300×890×1190 |
1700×1250×1650 |
660×820 |
|
SCB13-800 |
800 |
2035 |
1380×890×1320 |
1800×1300×1700 |
660×820 |
|
SCB13-1000 |
1000 |
2480 |
1450×890×1350 |
1900×1400×1800 |
820×820 |
|
SCB13-1250 |
1250 |
2730 |
1500×890×1410 |
1900×1400×1800 |
820×820 |
|
SCB13-1600 |
1600 |
3525 |
1640×1020×1475 |
2000×1500×2000 |
820×950 |
|
SCB13-2000 |
2000 |
3945 |
1750×1020×1580 |
2100×1600×2000 |
820×950 |
|
SCB13-2500 |
2500 |
4860 |
1910×1120×1960 |
2300×1600×2200 |
1070×1070 |
Note: The above data is for reference only. Our company reserves the right to change the data. Our company provides non-standard products according to user requirements.
Keyword:
Power equipment, power electrical equipment