SZ11-1000-31 500/35 Three Phase Oil Immersed On-load Voltage Regulation Power Transformer
Summary:
Product Category:
Tel:
SZ11-1000-31 500/35 Three Phase Oil Immersed On-load Voltage Regulation Power Transformer
Details
Model & Symbol Meaning

Executive Standards
●GB1094.1~2013
●GB1094.3.5~2017
●GB/T6451-2015
Overview
This product is suitable for substation design three-phase, 50HZ,35KV class and below the power system, is the main substation equipment for medium and small substation. This product is used for industrial and agricultural power distribution, power and lighting. This company absorbs the domestic and foreign advanced technology, uses the new material, the optimization design, causes the product to be more reasonable. The electrical strength, mechanical strength and heat dissipation capacity of the products have been significantly improved.
Performance Characteristics
●The HV winding adopts multi-layer cylinder structure to improve the impact distribution of the winding.
●The LV system group with a capacity of 630-3150kva adopts cylindrical or spiral structure, with high mechanical strength, balanced ampere-turns distribution and strong short-circuit capability.
●The positioning mechanism is added to the body of the device, so that it does not shift during transportation, and all fasteners are equipped with fastening nuts to ensure that the fasteners do not loosen during long-term operation and meet the requirements of not lifting the core.
●High quality cold rolled grain oriented silicon steel is adopted as the core and the transformer is vacuum oiled.
●After oil removal, rust removal and phosphating treatment, the product code can be sprayed with primer and paint-free paint to meet the special requirements of metallurgy, petrochemical systems and wet and dirty areas. The whole series of products are beautiful in appearance, small in size, small in occupied area for installation, and are ideal maintenance-free products.
SZ11-(M)-1000~31500/35 Three Phase Oil Immersed On-load Voltage Regulation Power Transformer Technical Parameters
|
Rated Capacity (kva) |
Voltage Combination |
Connection Group Mark |
No-oadLoss(kw) |
LoadLoss(kw) |
Short Circuit Impedance |
No-oad Current |
Body Weight/kVA |
Oil Weight(kVA) |
Total Weight/KVA) |
Total Weight |
Outline Dimension LxW×H(mm) |
Gauge (mm) |
||
|
High Yoltage |
Tapping Range |
Low Yoltage |
||||||||||||
|
1000 |
|
|
|
|
1.3 |
11.1 |
|
1.1 |
2125 |
1365 |
5060 |
4015 |
2965×2010×2530 |
070×1070 |
|
1250 |
|
|
|
|
1.6 |
14.2 |
|
1.1 |
2420 |
1450 |
5445 |
4180 |
3015×2030×2550 |
1070×1070 |
|
1600 |
35 |
|
|
|
1.9 |
17.0 |
6.5 |
1.0 |
2805 |
1540 |
5830 |
4378 |
3070×2060×2590 |
1070×1070 |
|
2000 |
|
|
10.5 |
Yd11 |
2.3 |
19.2 |
|
1.0 |
3050 |
1720 |
6560 |
5410 |
3130×2150×6490 |
1070×1070 |
|
2500 |
|
|
6.3 |
|
2.7 |
20.6 |
|
1.0 |
3630 |
1925 |
7645 |
6250 |
3160×2355×2715 |
1070×1070 |
|
3150 |
|
|
|
|
3.2 |
24.6 |
|
0.9 |
4150 |
2165 |
8690 |
6680 |
2865×2180×2750 |
1070×1070 |
|
4000 |
|
|
|
|
3.9 |
29.0 |
7.0 |
0.9 |
4970 |
2490 |
10020 |
7810 |
3425×2420×3010 |
1070×1070 |
|
5000 |
|
±3×2.5 |
|
|
4.6 |
34.0 |
|
0.8 |
6030 |
2730 |
11950 |
9310 |
3485×2620×3210 |
1070×1070 |
|
6300 |
|
|
|
|
5.5 |
36.6 |
|
0.8 |
7490 |
2885 |
13530 |
10860 |
3615×2750×3175 |
1070×1070 |
|
8000 |
|
|
|
|
7.7 |
40.4 |
7.5 |
0.7 |
8870 |
3670 |
16830 |
13810 |
4785×3250×3410 |
475×1475 |
|
10000 |
35 |
|
6.3 |
|
9.1 |
47.8 |
|
0.7 |
10670 |
4125 |
19645 |
16170 |
4890×3280×3535 |
1475×1475 |
|
12500 |
38.5 |
|
6.6 |
|
18.0 |
56.6 |
|
0.6 |
12060 |
4630 |
22055 |
19070 |
5045×3320×3570 |
1475×1475 |
|
16000 |
|
|
10.5 |
YNd11 |
12.0 |
70.0 |
|
0.6 |
15345 |
5390 |
26565 |
23100 |
5110×3950×3830 |
475×1475 |
|
20000 |
|
|
11 |
|
16.0 |
83.0 |
|
0.5 |
18370 |
6730 |
33110 |
27720 |
5150×3960×3840 |
475×1475 |
|
25000 |
|
|
|
|
18.0 |
98.5 |
|
0.5 |
21780 |
9350 |
40150 |
31570 |
5250×4060×4010 |
1475×1475 |
|
31500 |
|
|
|
|
21.0 |
117.0 |
|
0.45 |
28930 |
109620 |
51480 |
43800 |
5340×4215×4080 |
2040×1475 |
Notice:
1. Contact company for large volume 35kV transformer performance parameters, dimensions and weight data;
2. Customized voltage combination, short circuit resistance and connection method;
3. 8000kVA and above capacity transformers can install cooling system according requirements(Model SFZ11);
4. Data from table is for reference.